What pumped hydro storage does
A pumped hydro plant stores electricity as water held high up. When power is cheap or plentiful, pumps lift water from a lower reservoir to an upper one. When power is needed, the water runs back down through turbines and makes electricity again. It is the most common way to store large amounts of energy for the power grid, for many hours at a time.
The animation is a cutaway of a hill. One 12 second loop shows the two jobs in turn: first generating, then pumping. The machine that does both is a cousin of the centrifugal pump, and the turbine side uses the same idea as the turbines in the Rankine cycle, with falling water instead of steam. A battery site next to the plant, standing on the surface, is the fast partner: see battery energy storage.
How it works
Follow the water from the top reservoir, down the tunnel, through the machine and out to the lower reservoir. When the plant pumps, everything runs the other way.
- 1Upper reservoir. Holds the stored water high above the machines. The energy stored is the weight of the water times the height: more water, or water that sits higher, means more energy. The reservoir is a basin built into a hilltop, a lake or an old mine pit. Its level falls while the plant generates and rises while it pumps.
- 2Intake and penstock. The water enters through an intake with a grating that keeps out branches and debris, and gates that close it. A penstock, a steel-lined pressure tunnel or pipe, carries it down. At the bottom it holds the pressure of the whole column of water above it. A sudden stop of the flow sends a pressure wave through the water (water hammer), so the machine's valves close slowly and some plants add a surge shaft to soak up the wave.
- 3Reversible pump-turbine. One runner does both jobs. Generating: water flows around a spiral case, through guide vanes onto the runner and turns it. Pumping: the motor turns the runner the opposite way and it throws the water out into the penstock and up the hill. The machine is set below the lower water level, so the water always presses on its inlet. Without that the water could boil into vapour bubbles at the runner (cavitation) and damage it.
- 4Motor-generator. It sits on the same vertical shaft, above the runner. Generating, the shaft turns the rotor inside the copper windings of the stator and makes electricity. Pumping, the same machine takes electricity from the grid and works as a motor. It needs a way to be brought up to speed before it can pump. Some plants use a machine whose speed can vary, so that the power taken when pumping can be adjusted.
- 5Transformer and grid connection. The generator works at a voltage of typically 10,000 to 25,000 volts. A transformer raises it to the grid voltage, usually over a hundred kilovolts, and a cable in a shaft carries it up to the overhead line. When the plant pumps, power flows the other way and the transformer lowers the voltage for the motor.
- 6Draft tube, tailrace and lower reservoir. Water leaves the runner through the draft tube, a bend that widens so the water slows down and its speed turns back into pressure. The tailrace tunnel takes it to the lower reservoir, a lake, a river reservoir or a basin made for the purpose. It has to hold the whole volume that the upper reservoir releases. When the plant pumps, the water is drawn from here.
- 7The fast partner. A battery site next to the plant answers within a fraction of a second but stores for a few hours. A pumped hydro plant takes a few minutes to start but stores for many hours. Together they cover both short swings and long gaps in the supply. Click the battery container in the animation to open its lesson.
The numbers
Typical features of a pumped hydro plant: a head (the height between the two water levels) from about 100 m to over 700 m, a power from about 100 MW to over 1,000 MW, storage of typically 6 to 20 hours at full power, and a round-trip efficiency (electricity out divided by electricity in) of typically 70 to 80 percent. The plant can go from standstill to full power in a few minutes. All of these depend strongly on the site.
The stored energy is E = ρ × g × H × V: water density (1,000 kg/m³) times gravity (9.81 m/s²) times head (m) times volume (m³), in joules. One megawatt-hour is 3.6 × 109 J.
Worked example. Assume a gross head of 400 m, a usable volume of 3,000,000 m³ in the upper reservoir, a head loss in the tunnels of 3 percent of the head in each direction, an efficiency of 90 percent for the runner and generator together when generating, 90 percent for the motor and pump together when pumping, 10 hours of generating, 12 hours of pumping and a penstock diameter of 4.5 m.
| Quantity | Working | Result |
|---|
| Ideal stored energy | 1,000 × 9.81 × 400 × 3,000,000 = 1.177 × 1013 J; ÷ 3.6 × 109 J per MWh | about 3,270 MWh |
| Net head when generating | 400 × (1 − 0.03) | 388 m |
| Energy to the grid | 3,270 × 0.97 × 0.90 | about 2,855 MWh |
| Head to pump against | 400 × (1 + 0.03) | 412 m |
| Electricity used to pump the water up | 3,270 × 1.03 ÷ 0.90 | about 3,742 MWh |
| Round-trip efficiency | 2,855 ÷ 3,742 | about 0.76, or 76 percent |
| Flow when generating for 10 hours | 3,000,000 ÷ (10 × 3,600 s) | 83.3 m³/s |
| Electrical power when generating | 2,855 ÷ 10 h (check: 0.90 × 1,000 × 9.81 × 83.3 × 388 = 285 MW) | about 285 MW |
| Pumping power and flow over 12 hours | 3,742 ÷ 12 h; 3,000,000 ÷ (12 × 3,600 s) | about 312 MW; 69.4 m³/s |
| Water speed in the penstock when generating | area π × 4.5² ÷ 4 = 15.9 m²; 83.3 ÷ 15.9 | about 5.2 m/s |
The plant uses about 3,742 MWh to give back 2,855 MWh. The difference, about 887 MWh, is lost as friction in the tunnels and as heat in the pump, the turbine, the generator and the transformer. It pays when the power sold at the evening peak earns more than the power taken at night costs, by more than that loss.
Assumed inputs, not data from a particular plant. A real plant has several units, losses that change with the load, and water that evaporates or leaks. Typical ranges only.
Safety: a pumped hydro plant combines large volumes of water, steel-lined pressure tunnels, rotating machines and high voltage. Water levels, tunnel entry, machine isolation and electrical work follow the owner's own written procedures and permits. A release of water also changes the levels of lakes and rivers downstream. This lesson shows principles, not a design or an operating method.
What the operator watches
- Reservoir levels. Both levels set how much energy is stored and how much room is left. Limits protect the banks, the intake and the lower reservoir's own uses.
- Unit mode and power. Which units are generating, pumping or stopped, and how the power follows the grid operator's instructions.
- Vibration and bearing temperature. Rising values warn of wear, an unbalanced rotor or a failing bearing.
- Penstock pressure and gate position. Pressure that does not match the gate or the load can mean a blockage or a leak.
- Grid frequency and price signal. They decide when to pump and when to generate.
Common problems
- Water hammer. Closing a valve or tripping a unit too quickly sends a pressure wave through the tunnel. Slow closing times and surge shafts limit it.
- Cavitation. If the water pressure at the runner inlet is too low, vapour bubbles form and collapse and pit the metal. The machine is set low enough to avoid it.
- Wear from sand and grit. Fine particles in the water wear the runner, the guide vanes and the seals.
- Leakage and seepage. Water that escapes from a reservoir or a tunnel is lost energy and can damage the rock around it.
- Many starts and stops. Changing between pumping and generating many times a day tires the machine, so the number of starts is watched.
Words you will meet
- Head
- The height between the upper and lower water levels, in metres.
- Penstock
- The steel-lined pressure tunnel or pipe that carries the water to the machine.
- Reversible pump-turbine
- One runner that works as a turbine in one direction and as a pump in the other.
- Motor-generator
- One electrical machine that works as a generator or as a motor.
- Draft tube
- A widening bend below the runner that slows the water and regains pressure.
- Tailrace
- The tunnel or channel that links the machine to the lower reservoir.
- Round-trip efficiency
- Electricity returned to the grid divided by electricity taken to pump.
- Cavitation
- Vapour bubbles that form at low pressure and damage metal when they collapse.
Check your understanding
Why is the machine set below the level of the lower reservoir?
So that the water presses on the inlet of the pump with some margin. Without that pressure the water can form vapour bubbles at the runner (cavitation), which damages the metal and cuts the flow.
Why is the round-trip efficiency well below 100 percent?
Energy is lost at every step: friction in the tunnels, the runner when it works as turbine and as pump, the generator and the motor, and the transformer. In the example about 24 percent is lost, mostly as heat.
Why does the runner turn the other way when the plant pumps?
When generating, the water pushes the runner round. When pumping, the motor must push the water, so the runner turns in the opposite direction and its blades throw the water outward and up the penstock. The same blades work both ways.