Reverse Osmosis Train

Feed through a filter and pump, membranes in vessels, clean permeate and brine.

Loading the animation…
You are watching a free lesson. A free account saves your progress and lets you mark lessons complete. Create a free account Sign in

What a reverse osmosis train does

Reverse osmosis (RO) makes clean water from salty or poor water by pushing it through a membrane. The membrane lets water molecules pass and holds back most of the dissolved salts. Two streams come out: clean water, called permeate, and a smaller, saltier stream called the concentrate or brine.

Plain osmosis moves water from the fresh side of a membrane to the salty side. Reverse osmosis forces it the other way, so it needs a pressure higher than the osmotic pressure of the water. The method is used for brackish groundwater, for seawater (see the seawater plant), for treated waste water that is being reused, and for the salty water that comes up with coal seam gas (see produced water treatment). The membranes are delicate, so the water must be clean when it arrives. An RO train is therefore the last part of a treatment line, behind steps such as those of a water treatment plant.

How it works

This lesson shows one RO train from feed to cleaning. The seawater plant lesson shows how such trains sit inside a whole desalination plant.

  1. 1Feed and cartridge filter. The feed arrives already pretreated, for example through a clarifier and sand filters. A small dose of antiscalant is mixed in to stop salts forming scale on the membranes. A cartridge filter, cut open in the drawing, is the last guard: it catches any grit that got through, so that nothing hard reaches the pump or the membranes.
  2. 2High-pressure pump. A multi-stage centrifugal pump raises the pressure of the feed above the osmotic pressure of the water, which is the pressure that would make water flow the other way. It is the biggest user of power in the train.
  3. 3Pressure vessels and membranes. The feed goes into a rack of pressure vessels. Each vessel holds several membrane elements in a row, end to end. The front vessel is cut open. Water crosses the membrane into a tube in the middle of each element, and the salt stays behind in the feed, so the water gets saltier along the vessel.
  4. 4Inside one element. Sheets of membrane are wound in a spiral around the central tube, with thin mesh spacers between them. The feed runs along the element between the sheets. The water that passes through the membrane is carried along inside the sheets to the central tube. One element is shown on its own so that the spiral can be seen.
  5. 5Permeate. The clean water leaves from the end of each vessel into a manifold and goes to a tank. It may get a final adjustment, such as its pH, before it is used.
  6. 6Concentrate and the control valve. The salty water that did not pass through the membranes leaves the far end of the vessels at almost the feed pressure and goes to disposal. A control valve in this line sets the pressure in the vessels, and so the recovery, which is the share of the feed that becomes permeate. A large plant can use the pressure left in the concentrate to help the pump, with an energy recovery device (see the seawater plant).
  7. 7Cleaning in place. Scale and fine solids slowly build up on the membranes. When the clean-water flow falls or the pressure drop rises, the train is stopped and a cleaning solution is circulated through the vessels from a cleaning tank, without taking the membranes out. It is not used in normal running.

Why the recovery has a limit

The more of the feed that becomes permeate, the saltier the concentrate gets, and the higher its osmotic pressure. At some point the pump pressure is hardly above the osmotic pressure at the end of the vessel and little more water will pass. Before that point, the salts in the concentrate reach the limit of what water can hold and start to form scale on the last elements. So the recovery is set by the osmotic pressure and by scaling, and the control valve is adjusted to stay below both.

The numbers

Figures are typical and change with the water and the design. Brackish water is typically about 1,000 to 10,000 mg/L of salt. It is treated at about 10 to 30 bar (1 to 3 MPa) with a recovery of about 50 to 85 percent. Seawater is typically about 35,000 mg/L of salt, is treated at about 55 to 70 bar (5.5 to 7 MPa), and recovers only about 40 to 50 percent. A modern membrane typically holds back about 98 to 99.8 percent of the salt.

A cartridge filter is typically rated at about 1 to 5 micrometres. A common element is about 200 mm across (8 inch) and about 1 m long, with about 37 m² of membrane wound inside it. A vessel typically holds 6 to 8 elements in a row; the drawing shows three. The flux, the flow of permeate through each square metre of membrane, is typically about 15 to 25 L/(m²·h) for brackish water, and lower for seawater. As a rule of thumb, the osmotic pressure is about 0.077 MPa for every 1,000 mg/L of salt.

Worked example: a brackish water train

Assumed inputs: feed 200 m³/h of brackish water with 2,500 mg/L of salt (2.5 kg/m³); recovery 75 percent; 1 percent of the salt in the feed passes into the permeate; antiscalant dose 3 mg/L (3 g/m³); feed pressure 1.5 MPa; pump efficiency 80 percent; flux 20 L/(m²·h); 37 m² of membrane in each element; 6 elements in each vessel.

QuantityWorkingResult
Permeate flow200 × 0.75150 m³/h
Concentrate flow200 − 15050 m³/h
Antiscalant used3 g/m³ × 200 m³/h600 g/h (0.6 kg/h)
Salt in the feed200 × 2.5 kg/m³500 kg/h
Salt in the permeate1 percent of 500 = 5 kg/h, ÷ 150 m³/h0.033 kg/m³, about 33 mg/L
Salt in the concentrate500 − 5 = 495 kg/h, ÷ 50 m³/h9.9 kg/m³, about 9,900 mg/L (about 4 times the feed)
Osmotic pressure of the concentrate9.9 × 0.077 MPaabout 0.76 MPa, below the 1.5 MPa that the pump gives
Hydraulic power of the pump(200 ÷ 3,600 m³/s) × 1,500 kPaabout 83.3 kW
Power at the pump shaft83.3 ÷ 0.80about 104 kW
Energy for each m³ of permeate104.2 kW ÷ 150 m³/habout 0.69 kWh/m³
Membrane area150 m³/h = 150,000 L/h, ÷ 20 L/(m²·h)7,500 m²
Number of elements7,500 ÷ 37202.7, so 203 elements
Number of vessels203 ÷ 633.8, so 34 vessels (204 elements)

The concentrate is about four times as salty as the feed, and it is the last elements of each vessel that meet it. That is where scale starts, and it is why the recovery cannot simply be pushed higher. Note also that the pressure has to beat the osmotic pressure of the concentrate, not of the feed.

Assumed inputs, not data from a particular plant. The salt content, the recovery, the pressure, the flux and the membrane performance change with the water and the design. The drawing leaves out the feed pump, the valves, the instruments, the second stage that many plants add, and the energy recovery device. The vessels hold fewer elements than a real one.

Safety: water at membrane pressure can injure, and a vessel holds that pressure. Antiscalant and cleaning chemicals, which include acids and alkalis, are corrosive. The design relies on pressure relief, interlocks, bunding and permits to work. This lesson explains the principle and is not an operating procedure.

What the operator watches

  • Permeate flow and its salt content. A fall in flow means fouling or scaling. A rise in salt content means damaged membranes or a leaking seal. The salt content is usually followed by measuring conductivity.
  • Pressure drop across the vessels. A rise shows that deposits are filling the feed channels. A rise of about 15 percent over the start-up value is a typical sign that cleaning is due.
  • Normalised permeate flow. This is the flow corrected for temperature and pressure. Cold water is harder to push through, by roughly 2 to 3 percent for each degree Celsius, so the raw flow alone can mislead. A fall of about 10 percent is a typical trigger to clean.
  • The quality of the feed. The pressure drop of the cartridge filter, the turbidity and the antiscalant dose show whether the membranes are being protected.

Common problems

  • Scaling. Salts such as calcium carbonate come out of the concentrate and form a hard layer on the membrane, most of all at the end of the vessel where the concentrate is strongest.
  • Fouling. Fine solids, oil or a film of bacteria cover the membrane and block the flow.
  • Membrane damage. Oxidising chemicals such as chlorine damage a typical membrane, so any chlorine used upstream is removed before the water reaches it. Hard grit and a sudden start of the pump also do harm.
  • Leaks and seal failure. Feed leaks past a worn seal between elements into the permeate, and the salt content of the permeate rises.

Words you will meet

Reverse osmosis
Pushing water through a membrane at high pressure so that the salt stays behind.
Permeate
The clean water that has passed through the membrane.
Concentrate (brine)
The salty water left behind. It leaves at nearly the feed pressure.
Osmotic pressure
The pressure that would push water the other way, from the fresher side to the saltier side.
Recovery
The share of the feed that becomes permeate.
Rejection
The share of the salt that the membrane holds back.
Flux
The permeate flow through each square metre of membrane.
Spiral-wound element
Membrane sheets wound around a central tube, the usual form of an RO membrane.
Antiscalant
A chemical that stops scale forming on the membrane.
Cleaning in place
Washing the membranes with a cleaning solution without taking them out.

Check your understanding

Why must the pump pressure be higher than the osmotic pressure of the concentrate?

Osmotic pressure pushes water from the fresh side to the salty side, the wrong way. Only a pressure above it, with some extra to drive the flow, pushes water through from the salty side to the fresh side. The concentrate at the end of the vessel is the saltiest, so it has the highest osmotic pressure.

Closing the concentrate control valve a little raises the pressure in the vessels. What happens to the permeate flow and to the saltiness of the concentrate?

More water is pushed through, so the permeate flow and the recovery rise. The concentrate leaves in a smaller flow and is saltier, which raises its osmotic pressure and the risk of scale.

The pressure drop across the vessels rises and the normalised permeate flow falls. What has probably happened?

The membranes are fouling or scaling. The train is stopped and cleaned in place from the cleaning tank. It is also worth checking the cartridge filter and the antiscalant dose, to see why the membranes were not protected.

Key facts

The idea
A pump pushes water through a membrane that holds the salt back.
Two streams
Clean permeate, and a smaller stream of salty concentrate.
Pressure
Typically about 10 to 30 bar for brackish water and about 55 to 70 bar for seawater.
Recovery
Typically about 50 to 85 percent for brackish water and about 40 to 50 percent for seawater.
Protection
Pretreatment, a cartridge filter and antiscalant in front, and cleaning in place when the membranes foul.
Use the animation
Follow the numbers 1–7 on the drawing: they match the steps on this page, in the same order. Blue pipes carry the feed water, light blue pipes the clean permeate, brown pipes the concentrate and purple the chemicals. Look into the cut-open front vessel: pale dots show water crossing into the central tube, and brown dots, the salt, stay behind in the water that moves on. The element on its own shows the spiral. The red valve sets the pressure and the recovery. Click the pump to open its own lesson. Hover over any part for its name and what it does. The cleaning tank is not used in normal running.